IMPORTANT
The SBC 5110 and SBC 5210 hardware platforms are no longer supported beginning with the 10.0.0R0 release. This release supports SBC 5400/7000/SWe platforms. Contact Ribbon Sales for upgrade information.
This section contains environmental and power requirements for site planning in installing the SBC 5x10 platforms.
Site Environmental Requirements
The following table lists the environmental requirements for the
Unable to show "metadata-from": No such page "_space_variables"
.
Site Environmental Requirements
Item | Requirement |
---|
Rack Dimensions | - Maximum width: 17.16 inches, excluding mounting ears
- Maximum depth: 21 inches, excluding cable bend radius
- Maximum height: 3.44 inches
- Weight: 50 lbs
- Mounts in 19-inch or 23-inch racks
|
Server Access Clearance | A minimum of 36-inch clearance in front of and behind the chassis. |
Humidity | Short-Term Operating - 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).
NOTE: Short-term is defined as 96 consecutive hours or less, and not more than 15 days in a year. |
Full-Term Operating |
Non-operating - Up to 93% non-condensing 100.4° F (37.7° C) maximum wet bulb.
|
Temperature | Operating 41° F to 104° F (5° C to 40° C) up to 6,000 feet (1,829 meters) Short-Term: 28° F to 131° F (-5° C to 55° C) up to 6,000 feet (1,829 meters). NOTE: Short-term is defined as 96 consecutive hours or less and not more than 15 days in a year. |
Non-Operating -40° F to 158° F (-40° C to 70° C) |
Elevation | Operating -197 feet to 6,000 feet (-60 to 1,800 meters) at 104° F (40° C). 5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86° F (30° C) |
Rack Space | Width: 17.16 inch excluding mounting ears Height: 3.44 inch to fit in 2 RU (3.5 inch) Depth: 21 inch excluding cable bend radius Weight: 50 lbs Mounts in 19 or 23 inch racks |
Vibration profiles | Operating 0.1G, 5-100 Hz, 0.1 octave/min 0.1G (x,y axis); 0.15G (z axis), 5-500 Hz, 1 octave/min |
Non-operating 5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3 dB/octave |
Site Power Requirements
The following table lists the SBC 5000 system power requirements:
SBC 5000 Series System Power Requirements
| SBC 5100 | SBC 5200 | SBC 5110 | SBC 5210 |
---|
DC Option |
---|
Operational DC Voltage (Nominal) | -48 | -48 | -48 | -48 |
---|
Operational DC voltage (Minimal) | -40 | -40 | -40 | -40 |
---|
Operational DC voltage (Maximum) | -72 | -72 | -72 | -72 |
---|
DC Input Treatment | Isolated DC Return | Isolated DC Return | Isolated DC Return | Isolated DC Return |
---|
Maximum DC Current | 15 A | 19 A | 24 A | 36.2 A |
---|
AC Option |
---|
Operational AC Voltage (Nominal) | 100-120 VAC @ 50-60 Hz or 200-240 VAC @ 50-60 Hz | 100-120 VAC @ 50-60 Hz or 200-240 VAC @ 50-60 Hz | 100-120 VAC @ 50-60 Hz or 200-240 VAC @ 50-60 Hz | 100-120 VAC @ 50-60 Hz or 200-240 VAC @ 50-60 Hz |
---|
Maximum AC Current | 7.1 A / 3.4 A | 8.5 A / 4.1 A | 12 A / 7 A | 12 A / 7 A |
---|
Power Cord |
(North American 15 A 125 Volt NEMA 5-15P to IEC C19 connector) |
---|
Grounding |
---|
Bonding | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). |
---|
Note
SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process. The example above is a North American power cord (15 amp 125 volt NEMA 5-15P to IEC C19 connector), which is one of the selections.