In this section:

 


IMPORTANT

The SBC 5110 and SBC 5210 hardware platforms are no longer supported beginning with the 10.0.0R0 release. This release supports SBC 5400/7000/SWe platforms. Contact Ribbon Sales for upgrade information.

This section contains environmental and power requirements for site planning in installing the SBC 5x10 platforms.

Note

The SBC 5400 site planning details are listed separately on the page SBC 5400 Site Planning and Requirements.


Site Environmental Requirements

The following table lists the environmental requirements for the SBC 5000 series.

Site Environmental Requirements

Item

Requirement

Rack Dimensions

  • Maximum width: 17.16 inches, excluding mounting ears
  • Maximum depth: 21 inches, excluding cable bend radius
  • Maximum height: 3.44 inches
  • Weight: 50 lbs
  • Mounts in 19-inch or 23-inch racks

Server Access Clearance

A minimum of 36-inch clearance in front of and behind the chassis.

Humidity

  

Short-Term Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

NOTE: Short-term is defined as 96 consecutive hours or less, and not more than 15 days in a year.

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4° F (37.7° C) maximum wet bulb.

Temperature

Operating

41° F to 104° F (5° C to 40° C) up to 6,000 feet (1,829 meters)
Short-Term: 28° F to 131° F (-5° C to 55° C) up to 6,000 feet (1,829 meters).

NOTE: Short-term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Non-Operating
-40° F to 158° F (-40° C to 70° C)

Elevation

Operating

-197 feet to 6,000 feet (-60 to 1,800 meters) at 104° F (40° C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86° F (30° C)

Rack Space

Width: 17.16 inch excluding mounting ears
Height: 3.44 inch to fit in 2 RU (3.5 inch)
Depth: 21 inch excluding cable bend radius
Weight: 50 lbs
Mounts in 19 or 23 inch racks

Vibration profiles

Operating

0.1G, 5-100 Hz, 0.1 octave/min
0.1G (x,y axis); 0.15G (z axis), 5-500 Hz, 1 octave/min

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3 dB/octave

 


Site Power Requirements

The following table lists the SBC 5000 system power requirements:


SBC 5110

SBC 5210

DC Requirements

Operational DC Voltage (Nominal)

-48

-48

Operational DC voltage (Minimal)

-40

-40

Operational DC voltage (Maximum)

-72

-72

DC Input Treatment

Isolated DC Return

Isolated DC Return

Maximum DC Current

24 A

36.2 A

AC Requirements

Operational AC Voltage (Nominal)

100-120 VAC @ 50-60 Hz
or 
200-240 VAC @ 50-60 Hz

100-120 VAC @ 50-60 Hz
or 
200-240 VAC @ 50-60 Hz

Maximum AC Current

12 A / 7 A

12 A / 7 A

Power Cord

(North American 15 A 125 Volt NEMA 5-15P to IEC C19 connector)

Grounding

BondingBonded to a grounding system utilizing either an Isolated Bonding Network
(Isolated Ground) or a Common Bonding Network (Integrated Ground).


  • No labels