This section contains information on site planning and requirements for installing the

Unable to show "metadata-from": No such page "_space_variables"
system.

Site Environmental Requirements

The following table lists the environmental requirements for the

Unable to show "metadata-from": No such page "_space_variables"
platform.

Site Environmental Requirements

Item

Requirement

Server Access Clearance

A minimum clearance of 36 inches in front of and behind the chassis for maintenance access as well as air flow.

Humidity

  

Short-Term* Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.

Temperature

Operating

41°F to 104°F (5°C to 40°C) up to 6,000 feet (1,829 meters)
Short-Term*: 28°F to 131°F (-5°C to 55°C) up to 6,000 feet (1,829 meters).

Non-Operating

-40°F to 158°F (-40°C to 70°C)

Elevation

Operating

-197 feet to 6,000 feet (-60 to 1,800 meters) at 104°F (40°C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86°F (30°C)

Rack Space

Width: 17.16 inch excluding mounting ears
Height: 3.44 inch to fit in 2RU (3.5 inch)
Depth: 21-inch, excluding cable bend radius
Weight: 50 pounds
Mounts in 19-inch or 23-inch racks

Vibration Profiles

Operating

0.1G, 5-100Hz, 0.1 Oct/min
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave

*  Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Site Power Requirements

The following table lists the 

Unable to show "metadata-from": No such page "_space_variables"
system power requirements for both AC and DC power options:

SBC 5400 System Power Requirements

 

SBC 5400

DC Option

Operational DC Voltage (Nominal)

-48

Operational DC voltage (Minimal)

-40

Operational DC voltage (Maximum)

-72

DC Input Treatment

Isolated DC Return

Maximum DC Current

36.2 A

AC Option

Operational AC Voltage (Nominal)

100-120 VAC @ 50-60 Hz
or 
200-240 VAC @ 50-60 Hz

Maximum AC Current

12 A / 7 A

Power Cord

An AC power cord is included in SBC shipments for SBCs equipped with AC power supplies.

(North American 15 A 125 VOLT NEMA 5-15P to IEC C19 Connector)

Grounding

BondingBonded to a grounding system utilizing either an Isolated Bonding Network
(Isolated Ground) or a Common Bonding Network (Integrated Ground).

Note

SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process.  The example above is a North American power cord (15 amp 125 volt NEMA 5-15P to IEC C19 connector), which is one of the selections.

 