This section contains information on site planning and requirements for installing the

Spacevars
0model5
system.

Site Environmental Requirements

The following table lists the environmental requirements for the

Spacevars
0model5
platform.

Caption0Table1Site Environmental Requirements


Item

Requirement

Server Access Clearance

A minimum clearance of 36 inches in front of and behind the chassis for maintenance access as well as air flow.

Humidity

  

Short-Term* Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.

Temperature

Operating

41°F to 104°F (5°C to 40°C) up to 6,000 feet (1,829 meters)
Short-Term*: 28°F to 131°F (-5°C to 55°C) up to 6,000 feet (1,829 meters).

Non-Operating

-40°F to 158°F (-40°C to 70°C)

Elevation

Operating

-197 feet to 6,000 feet (-60 to 1,800 meters) at 104°F (40°C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86°F (30°C)

Rack Space

Width: 17.16 inch excluding mounting ears
Height: 3.44 inch to fit in 2RU (3.5 inch)
Depth: 21-inch, excluding cable bend radius
Weight: 50 pounds
Mounts in 19-inch or 23-inch racks

Vibration Profiles

Operating

0.1G, 5-100Hz, 0.1 Oct/min
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave


Note
iconfalse

*  Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Site Power Requirements

The following table lists the 

Spacevars
0model5
system power requirements for both AC and DC power options: Caption
0Table
1SBC 5400 System Power Requirements
3SBC 5400 System Power Requirements

 

.


SBC 5400

DC Option

Operational DC Voltage (Nominal)

-48

Operational DC voltage (Minimal)

-40

Operational DC voltage (Maximum)

-72

DC Input Treatment

Isolated DC Return

Maximum DC Current

36.2 A

30 A

Info
titleNote

30A is the theoretical absolute Maximum current for the 1200W DC supply operating at -40VDC. The measured current values for an SBC 5400 running at high load with a max fan speed at -40VDC is 17.2A.


AC Option

Operational AC Voltage (Nominal)

100-120 VAC @ 50-60 Hz
or 
200-240 VAC @ 50-60 Hz

Maximum AC Current

12 A / 7 A

Power Cord

An AC power cord is included in SBC shipments for SBCs equipped with AC power supplies.

Image Modified

(North American 15 A 125 VOLT NEMA 5-15P to IEC C19 Connector)

Grounding

BondingBonded to a grounding system utilizing either an Isolated Bonding Network
(Isolated Ground) or a Common Bonding Network (Integrated Ground).


Info
titleNote

SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process.  The example above is a North American power cord (15 amp 125 volt NEMA 5-15P to IEC C19 connector), which is one of the selections.

 

pagebreak