This section contains site planning and requirements information for installing the
Unable to show "metadata-from": No such page "_space_variables"
system.
Site Environmental Requirements
The following table lists the environmental requirements of
Unable to show "metadata-from": No such page "_space_variables"
.
Site Environmental Requirements
Item | Requirement |
---|
SBC 7000 Dimension | - 19" Rack Width - 17.096" excluding mounting ears
- Maximum depth from Bezel badge label to power supply handle - 23.095"
- 5U High - 8.718 inches
- Weight: 98lbs
- Mounts in 19 or 23 inch racks
|
Rack Space | - 19" Rack Width - 17.096" excluding mounting ears
- Maximum depth from Bezel badge label to power supply handle - 23.095"
- 5U High - 8.718 inches
- Weight: 98lbs
- Mounts in 19 or 23 inch racks
|
Server Access Clearance | A minimum of 36 inch clearance in both front and rear of the chassis. |
Humidity | Short-Term Operating - 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).
Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.
|
Full-Term Operating |
Non-operating - Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.
|
Temperature | Operating 41°F to 104°F (5°C to 40°C) up to 6000 feet (1829 meters) Short-Term: 28°F to 131°F (-5°C to 55°C) up to 6000 feet (1829 meters).
Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.
|
| Non-Operating -40°F to 158°F (-40°C to 70°C) |
Elevation | Operating -197 feet to 6000 feet (-60 to 1800 meters) at 104°F (40°C). 5900 feet to 13100 feet (1800 to 4000 meters) at 86°F (30°C) |
Vibration profiles | Operating 0.1G, 5-100Hz, 0.1 Oct/min 0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min |
| Non-operating 5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave |
Site Power Requirements
The following table lists the
Unable to show "metadata-from": No such page "_space_variables"
system power requirements:
SBC 7000 System Power Requirements
| SBC 7000 |
---|
DC Option | |
---|
AC Option | - Operational AC Voltage (Nominal): 220 V AC
- Frequency: 50/60 Hz
- Maximum AC current for 220 V AC: 16A
|
---|
Grounding | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). |
---|
Connection to AC Power Source and Powering On
For using 220 V AC, the higher amperage AC connector is used, and it is different than a normal AC connector. The three blades higher amperage AC Connector is shown below.
High Amperage AC Connector