This section contains environmental and power requirements for site planning in installing the

Unable to show "metadata-from": No such page "_space_variables"
platforms.

The

Unable to show "metadata-from": No such page "_space_variables"
site planning details are listed separately on the page SBC 5400 Site Planning and Requirements.

 

Site Environmental Requirements

The following table lists the environmental requirements for the

Unable to show "metadata-from": No such page "_space_variables"
.

Site Environmental Requirements

Item

Requirement

Rack Dimensions

  • Maximum width - 17.16 inches, excluding mounting ears
  • Maximum depth - 21 inches, excluding cable bend radius
  • Maximum height - 3.44 inches
  • Weight: 50 lbs
  • Mounts in 19 or 23-inch racks

Server Access Clearance

A minimum of 36-inch clearance in front of and behind the chassis.

Humidity

  

Short-Term Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

NOTE: Short-term is defined as 96 consecutive hours or less, and not more than 15 days in a year.

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4° F (37.7° C) maximum wet bulb.

Temperature

Operating
41° F to 104° F (5° C to 40° C) up to 6,000 feet (1,829 meters)
Short-Term: 28° F to 131° F (-5° C to 55° C) up to 6,000 feet (1,829 meters).

NOTE: Short-term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Non-Operating
-40° F to 158° F (-40° C to 70° C)

Elevation

Operating
-197 feet to 6,000 feet (-60 to 1,800 meters) at 104° F (40° C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86° F (30° C)

Rack Space

Width: 17.16 inch excluding mounting ears
Height: 3.44 inch to fit in 2 RU (3.5 inch)
Depth: 21 inch excluding cable bend radius
Weight: 50 lbs
Mounts in 19 or 23 inch racks

Vibration profiles

Operating
0.1G, 5-100 Hz, 0.1 octave/min
0.1G (x,y axis); 0.15G (z axis), 5-500 Hz, 1 octave/min

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3 dB/octave

 

Site Power Requirements

The following table lists the SBC 5000 system power requirements:

SBC 5000 Series System Power Requirements

SBC 5200SBC 5210SBC 5100SBC 5110
DC Option
  • Operational DC Voltage (Nominal)
    for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC
  • DC Input treatment: Isolated
    DC Return
  • Maximum DC current: 19A
  • Operational DC Voltage
    (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC
  • DC Input treatment: Isolated
    DC Return
  • Maximum DC current: 36.2A
  • Operational DC Voltage
    (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC
  • DC Input treatment: Isolated
    DC Return
  • Maximum DC current: 15A
  • Operational DC Voltage
    (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC

  • DC Input treatment: Isolated
    DC Return

  • Maximum DC current: 24A

AC Option
  • Operational AC Voltage (Nominal):
    100-120 V AC or  200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 8.5A/4.1A
  • Operational AC Voltage (Nominal):
    100-120 V AC or  200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 12A/7A
  • Operational AC Voltage (Nominal):
    100-120 V AC or 200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 7.1A/3.4A
  • Operational AC Voltage (Nominal):
    100-120 V AC or 200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 12A/7A
Grounding

Bonded to a grounding system
utilizing either an Isolated 
Bonding Network
(Isolated Ground)
or a Common Bonding Network
(Integrated Ground).

Bonded to a grounding system utilizing
either an Isolated Bonding Network
(Isolated Ground) or a Common
Bonding Network (Integrated Ground).

Bonded to a grounding system
utilizing either an Isolated Bonding
Network (Isolated Ground) or a Common
Bonding Network (Integrated Ground).

 
 Bonded to a grounding system
utilizing either an Isolated Bonding
Network (Isolated Ground) or a Common
Bonding Network (Integrated Ground).