This section contains information on site planning and requirements for installing the

Unable to show "metadata-from": No such page "_space_variables"
system.

Site Environmental Requirements

The following table lists the environmental requirements for the

Unable to show "metadata-from": No such page "_space_variables"
.

Table 1: Site Environmental Requirements

Item

Requirement

Rack Dimensions

  • Maximum width - 17.16 inch excluding mounting ears
  • Maximum depth - 21 inch excluding cable bend radius
  • Maximum height - 3.44 inch
  • Weight: 50lbs
  • Mounts in 19 or 23 inch racks

Server Access Clearance

A minimum of 36 inch clearance in both front and rear of the chassis.

Humidity

  

Short-Term Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.

Temperature

Operating
41°F to 104°F (5°C to 40°C) up to 6000 feet (1829 meters)
Short-Term: 28°F to 131°F (-5°C to 55°C) up to 6000 feet (1829 meters).

Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

 

Non-Operating
-40°F to 158°F (-40°C to 70°C)

Elevation

Operating
-197 feet to 6000 feet (-60 to 1800 meters) at 104°F (40°C).
5900 feet to 13100 feet (1800 to 4000 meters) at 86°F (30°C)

Rack Space

Width: 17.16 inch excluding mounting ears
Height: 3.44 inch to fit in 2RU (3.5 inch)
Depth: 21 inch excluding cable bend radius
Weight: 50lbs
Mounts in 19 or 23 inch racks

Vibration profiles

Operating
0.1G, 5-100Hz, 0.1 Oct/min
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min

 

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave

Site Power Requirements

The following table lists the SBC 5000 system power requirements:

Table 2: SBC 5000 System Power Requirements.

 SBC 5200SBC 5210SBC 5100SBC 5110
DC Option
  • Operational DC Voltage (Nominal)
    for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC
  • DC Input treatment: Isolated
    DC Return
  • Maximum DC current: 19A
  • Operational DC Voltage
    (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC
  • DC Input treatment: Isolated
    DC Return
  • Maximum DC current: 36.2A
  • Operational DC Voltage
    (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC
  • DC Input treatment: Isolated
    DC Return
  • Maximum DC current: 15A
  • Operational DC Voltage
    (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC

  • DC Input treatment: Isolated
    DC Return

  • Maximum DC current: 24A

AC Option
  • Operational AC Voltage (Nominal):
    100-120 V AC or  200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 8.5A/4.1A
  • Operational AC Voltage (Nominal):
    100-120 V AC or  200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 12A/7A
  • Operational AC Voltage (Nominal):
    100-120 V AC or 200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 7.1A/3.4A
  • Operational AC Voltage (Nominal):
    100-120 V AC or 200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 12A/7A
Grounding

Bonded to a grounding system
utilizing either an Isolated 
Bonding Network
(Isolated Ground)
or a Common Bonding Network
(Integrated Ground).

Bonded to a grounding system utilizing
either an Isolated Bonding Network
(Isolated Ground) or a Common
Bonding Network (Integrated Ground).

Bonded to a grounding system
utilizing either an Isolated Bonding
Network (Isolated Ground) or a Common
Bonding Network (Integrated Ground).

 
 Bonded to a grounding system
utilizing either an Isolated Bonding
Network (Isolated Ground) or a Common
Bonding Network (Integrated Ground).