This section contains environmental and power requirements for site planning in installing the
Unable to show "metadata-from": No such page "_space_variables"
platforms.
Site Environmental Requirements
The following table lists the environmental requirements for the
Unable to show "metadata-from": No such page "_space_variables"
.
Site Environmental Requirements
Item | Requirement |
---|
Rack Dimensions | - Maximum width: 17.16 inches, excluding mounting ears
- Maximum depth: 21 inches, excluding cable bend radius
- Maximum height: 3.44 inches
- Weight: 50 lbs
- Mounts in 19-inch or 23-inch racks
|
Server Access Clearance | A minimum of 36-inch clearance in front of and behind the chassis. |
Humidity | Short-Term Operating - 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).
NOTE: Short-term is defined as 96 consecutive hours or less, and not more than 15 days in a year. |
Full-Term Operating |
Non-operating - Up to 93% non-condensing 100.4° F (37.7° C) maximum wet bulb.
|
Temperature | Operating 41° F to 104° F (5° C to 40° C) up to 6,000 feet (1,829 meters) Short-Term: 28° F to 131° F (-5° C to 55° C) up to 6,000 feet (1,829 meters). NOTE: Short-term is defined as 96 consecutive hours or less and not more than 15 days in a year. |
Non-Operating -40° F to 158° F (-40° C to 70° C) |
Elevation | Operating -197 feet to 6,000 feet (-60 to 1,800 meters) at 104° F (40° C). 5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86° F (30° C) |
Rack Space | Width: 17.16 inch excluding mounting ears Height: 3.44 inch to fit in 2 RU (3.5 inch) Depth: 21 inch excluding cable bend radius Weight: 50 lbs Mounts in 19 or 23 inch racks |
Vibration profiles | Operating 0.1G, 5-100 Hz, 0.1 octave/min 0.1G (x,y axis); 0.15G (z axis), 5-500 Hz, 1 octave/min |
Non-operating 5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3 dB/octave |
Site Power Requirements
The following table lists the SBC 5000 system power requirements:
SBC 5000 Series System Power Requirements
| SBC 5100 | SBC 5200 | SBC 5110 | SBC 5210 |
---|
DC Option |
---|
Operational DC Voltage (Nominal) | -48 | -48 | -48 | -48 |
---|
Operational DC voltage (Minimal) | -40 | -40 | -40 | -40 |
---|
Operational DC voltage (Maximum) | -72 | -72 | -72 | -72 |
---|
DC Input Treatment | Isolated DC Return | Isolated DC Return | Isolated DC Return | Isolated DC Return |
---|
Maximum DC Current | 15 A | 19 A | 24 A | 36.2 A |
---|
AC Option |
---|
Operational AC Voltage (Nominal) | 100-120 VAC @ 50-60 Hz or 200-240 VAC @ 50-60 Hz | 100-120 VAC @ 50-60 Hz or 200-240 VAC @ 50-60 Hz | 100-120 VAC @ 50-60 Hz or 200-240 VAC @ 50-60 Hz | 100-120 VAC @ 50-60 Hz or 200-240 VAC @ 50-60 Hz |
---|
Maximum AC Current | 7.1 A / 3.4 A | 8.5 A / 4.1 A | 12 A / 7 A | 12 A / 7 A |
---|
Power Cord |
(North American 15 A 125 Volt NEMA 5-15P to IEC C19 connector) |
---|
Grounding |
---|
Bonding | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). |
---|
Note
SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process. The example above is a North American power cord (15 amp 125 volt NEMA 5-15P to IEC C19 connector), which is one of the selections.