This section contains site planning and requirements information for installing the
Unable to show "metadata-from": No such page "_space_variables"
system.
Site Environmental Requirements
The following table lists the environmental requirements of
Unable to show "metadata-from": No such page "_space_variables"
.
Site Environmental Requirements
Item | Requirement |
---|
SBC 7000 Dimensions | - 19" Rack Width - 17.096" excluding mounting ears
- Maximum depth from Bezel badge label to power supply handle - 23.095"
- 5U High - 8.718 inches
- Weight: 98 lbs
- Mounts in 19 or 23-inch racks
|
Rack Space | - 19" Rack Width - 17.096" excluding mounting ears
- Maximum depth from Bezel badge label to power supply handle - 23.095"
- 5U high - 8.718 inches
- Weight: 98 lbs
- Mounts in 19 or 23-inch racks
|
Server Access Clearance | A minimum 36-inch clearance in front of and behind the chassis. |
Humidity | Short-Term Operating - 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).
NOTE: Short-term is defined as 96 consecutive hours or less, and not more than 15 days in 12 months. |
Full-Term Operating |
Non-operating - Up to 93% non-condensing 100.4° F (37.7° C) maximum wet bulb.
|
Temperature | Operating 41° F to 104° F (5° C to 40° C) up to 6,000 feet (1,829 meters) Short-term: 28° F to 131° F (-5° C to 55° C) up to 6,000 feet (1,829 meters). NOTE: Short-term is defined as 96 consecutive hours or less and not more than 15 days in 12 months. |
Non-Operating -40° F to 158° F (-40° C to 70° C) |
Elevation | Operating -197 feet to 6,000 feet (-60 to 1,800 meters) at 104° F (40° C). 5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86° F (30° C) |
Vibration profiles | Operating 0.1G, 5-100 Hz, 0.1 octave/minute 0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 octave/minute |
Non-operating 5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3 dB/octave |
Site Power Requirements
The following table lists the
Unable to show "metadata-from": No such page "_space_variables"
system power requirements:
SBC 7000 System Power Requirements
| Power Requirements |
---|
DC Option | NOTE: Prior to connecting to the DC power source, connect the (earth) ground at both the designated grounding terminals on the SBC 7000 chassis and at the facility wiring side of the DC supply. |
---|
AC Option | - Operational AC Voltage (Nominal): 220 V AC
- Frequency: 50/60 Hz
- Maximum AC current for 220 V AC: 16A
|
---|
Grounding | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). |
---|
Warning
For DC powered
Unable to show "metadata-from": No such page "_space_variables"
, the primary over-current protection is provided by the building circuit breaker. This breaker must not exceed 100A (recommended rating is 80A) and protects against excess currents, short circuits, and earth faults in accordance to national and/or local codes.
High Amp AC Power Connector
A higher amperage AC connector is used which is different than a normal AC connectors to power the Unable to show "metadata-from": No such page "_space_variables"
. The connector pin orientation of this higher amperage AC connector is shown below.
High Amperage AC Connector