Site Environmental Requirements
The following table lists the environmental requirements for the
Unable to show "metadata-from": No such page "_space_variables"
.
Table 1: Site Environmental Requirements
Item | Requirement |
---|
Rack Dimensions | - Maximum width - 17.16 inch excluding mounting ears
- Maximum depth - 21 inch excluding cable bend radius
- Maximum height - 3.44 inch
- Weight: 50lbs
- Mounts in 19 or 23 inch racks
|
Server Access Clearance | A minimum of 36 inch clearance in both front and rear of the chassis. |
Humidity | Short-Term Operating - 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).
Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.
|
Full-Term Operating |
Non-operating - Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.
|
Temperature | Operating 41°F to 104°F (5°C to 40°C) up to 6000 feet (1829 meters) Short-Term: 28°F to 131°F (-5°C to 55°C) up to 6000 feet (1829 meters).
Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.
|
| Non-Operating -40°F to 158°F (-40°C to 70°C) |
Elevation | Operating -197 feet to 6000 feet (-60 to 1800 meters) at 104°F (40°C). 5900 feet to 13100 feet (1800 to 4000 meters) at 86°F (30°C) |
Rack Space | Width: 17.16 inch excluding mounting ears Height: 3.44 inch to fit in 2RU (3.5 inch) Depth: 21 inch excluding cable bend radius Weight: 50lbs Mounts in 19 or 23 inch racks |
Vibration profiles | Operating 0.1G, 5-100Hz, 0.1 Oct/min 0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min |
| Non-operating 5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave |
Site Power Requirements
The following table lists the SBC 5000 system power requirements:
Table 2: SBC 5000 System Power Requirements.
| SBC 5200 | SBC 5210 | SBC 5100 | SBC 5110 |
---|
DC Option | - Operational DC Voltage (Nominal)
for chassis: -48 V DC - Minimum operation DC voltage for
chassis: -40 V DC - Maximum operation DC voltage for
chassis: -72 V DC - DC Input treatment: Isolated
DC Return - Maximum DC current: 19A
| - Operational DC Voltage
(Nominal) for chassis: -48 V DC - Minimum operation DC voltage for
chassis: -40 V DC - Maximum operation DC voltage for
chassis: -72 V DC - DC Input treatment: Isolated
DC Return - Maximum DC current: 36.2A
| - Operational DC Voltage
(Nominal) for chassis: -48 V DC - Minimum operation DC voltage for
chassis: -40 V DC - Maximum operation DC voltage for
chassis: -72 V DC - DC Input treatment: Isolated
DC Return - Maximum DC current: 15A
| |
---|
AC Option | - Operational AC Voltage (Nominal):
100-120 V AC or 200-240 V AC - Frequency: 50/60 hz
- Maximum AC current: 8.5A/4.1A
| - Operational AC Voltage (Nominal):
100-120 V AC or 200-240 V AC - Frequency: 50/60 hz
- Maximum AC current: 12A/7A
| - Operational AC Voltage (Nominal):
100-120 V AC or 200-240 V AC - Frequency: 50/60 hz
- Maximum AC current: 7.1A/3.4A
| - Operational AC Voltage (Nominal):
100-120 V AC or 200-240 V AC - Frequency: 50/60 hz
- Maximum AC current: 12A/7A
|
---|
Grounding | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). |
---|