In this section:
This section contains information on site planning and requirements for installing the SBC 5400 system.
Site Environmental Requirements
The following table lists the environmental requirements for the SBC 5400 platform.
Site Environmental Requirements
Item | Requirement |
---|---|
Server Access Clearance | A minimum clearance of 36 inches in front of and behind the chassis for maintenance access as well as air flow. |
Humidity | Short-Term* Operating
|
Full-Term Operating
| |
Non-operating
| |
Temperature | Operating 41°F to 104°F (5°C to 40°C) up to 6,000 feet (1,829 meters) |
Non-Operating -40°F to 158°F (-40°C to 70°C) | |
Elevation | Operating -197 feet to 6,000 feet (-60 to 1,800 meters) at 104°F (40°C). |
Rack Space | Width: 17.16 inch excluding mounting ears |
Vibration Profiles | Operating 0.1G, 5-100Hz, 0.1 Oct/min |
Non-operating |
Site Power Requirements
The following table lists the SBC 5400 system power requirements for both AC and DC power options:
SBC 5400 System Power Requirements
| SBC 5400 |
---|---|
DC Option | |
Operational DC Voltage (Nominal) | -48 |
Operational DC voltage (Minimal) | -40 |
Operational DC voltage (Maximum) | -72 |
DC Input Treatment | Isolated DC Return |
Maximum DC Current | 36.2 A |
AC Option | |
Operational AC Voltage (Nominal) | 100-120 VAC @ 50-60 Hz |
Maximum AC Current | 12 A / 7 A |
Power Cord | An AC power cord is included in SBC shipments for SBCs equipped with AC power supplies. (North American 15 A 125 VOLT NEMA 5-15P to IEC C19 Connector) |
Grounding | |
Bonding | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). |
SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process. The example above is a North American power cord (15 amp 125 volt NEMA 5-15P to IEC C19 connector), which is one of the selections.