The SBC 51xx and SBC 52xx platforms are not supported from release 11.0.0 onwards. This release supports the SBC 5400, SBC 7000 and SBC SWe platforms.
This section contains environmental and power requirements for site planning in installing the SBC 5x10 platforms.
The following table lists the environmental requirements for the SBC 5000 series.
The following table lists the SBC 5000 system power requirements:
SBC 5110 | SBC 5210 | |
---|---|---|
DC Requirements | ||
Operational DC Voltage (Nominal) | -48 | -48 |
Operational DC voltage (Minimal) | -40 | -40 |
Operational DC voltage (Maximum) | -72 | -72 |
DC Input Treatment | Isolated DC Return | Isolated DC Return |
Maximum DC Current | 24 A | 36.2 A |
AC Requirements | ||
Operational AC Voltage (Nominal) | 100-120 VAC @ 50-60 Hz | 100-120 VAC @ 50-60 Hz |
Maximum AC Current | 12 A / 7 A | 12 A / 7 A |
Power Cord | (North American 15 A 125 Volt NEMA 5-15P to IEC C19 connector) | |
Grounding | ||
Bonding | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). |