Install the EdgeMarc in a 19” rack using the rack mount kit supplied with the device.

Before You Begin   

Before installing the EdgeMarc in a rack, take note of the following conditions:

Elevated Operating Ambient—If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefore, make sure to install the equipment in an environment compatible with the maximum ambient temperature specified by the manufacturer.

Reduced Air Flow—Install equipment in a rack such that the amount of airflow required for safe operation of the equipment is not compromised.

Mechanical Loading—Mount the equipment in the rack such that a hazardous condition is not achieved due to uneven mechanical loading.

Circuit Overloading—Give consideration to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Use appropriate consideration of equipment nameplate ratings when addressing this concern.

Reliable Earthing—Maintain reliable earthing of rack-mounted equipment. Give particular attention to supply connections other than direct connections to the branch circuit (for example, use of power strips). Refer to Power Surge Protection and Grounding the EdgeMarc.

Install the EdgeMarc in a Rack

  1. Attach the rack mount ears to both sides of the EdgeMarc chassis with the supplied screws.
  2. Install the chassis in the rack with rack mount screws (not included).
  3. Connect the EdgeMarc to ground. Refer to Grounding the EdgeMarc.