This section describes the requirements for wiring of power connections to the SBC Edge (SBC).
For more information about grounding requirements for theSBC 1000/2000 see System Grounding Requirements. For more information the power supply units installed inside the SBC 1000/2000 chassis, see SBC Power Supplies.
Power Connections and Wiring
Provide AC power of nominal 120V/60Hz or 240V/50Hz for the equipment rack or shelf where the SBC is installed. For each line feed supplied to the rack or shelf, a dedicated primary branch circuit protection is required. SBC 1000/2000 equipment must be provided with dedicated branch circuit protection as a means of disconnecting the (electric) main to ensure the proper operation of and the safety of the persons servicing and operating this equipment. Therefore, the customer must provide an external circuit breaker that conforms to local electrical codes. Power connections to SBC 1000/2000 equipment must be provided from branch mains installed by a trained service personnel. For minimum wire requirements, see the tables below. Requirements Minimum Wire Size 14 AWG Minimum Voltage Rating 300 V Insulation PVC Conductor Stranded Requirements Minimum Wire Size 1.63 mm Minimum Voltage Rating 300 V Insulation PVC Conductor StrandedUnited States and Canada
Europe
Use only the AC power cord(s) supplied with the SBC.
Ribbon SBC 2000 Only: After the IEC power cord is plugged into the power supply module, secure by engaging the retaining clip over the power cord grip.