You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 4 Next »

In this section:

 

This section contains site planning and requirements information for installing the

Unable to show "metadata-from": No such page "_space_variables"
system.

Site Environmental Requirements

The following table lists the environmental requirements of

Unable to show "metadata-from": No such page "_space_variables"
.

Site Environmental Requirements

 

Item

Requirement

SBC 7000 Dimensions

  • 19" Rack Width - 17.096" excluding mounting ears
  • Maximum depth from Bezel badge label to power supply handle - 23.095"
  • 5U High - 8.718 inches
  • Weight: 98 lbs
  • Mounts in 19 or 23-inch racks
Rack Space
  • 19" Rack Width - 17.096" excluding mounting ears
  • Maximum depth from Bezel badge label to power supply handle - 23.095"
  • 5U high - 8.718 inches
  • Weight: 98 lbs
  • Mounts in 19 or 23-inch racks

Server Access Clearance

A minimum 36-inch clearance in front of and behind the chassis.

Humidity

  

Short-Term Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

NOTE: Short-term is defined as 96 consecutive hours or less, and not more than 15 days in 12 months.

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4° F (37.7° C) maximum wet bulb.

Temperature

Operating

41° F to 104° F (5° C to 40° C) up to 6,000 feet (1,829 meters)
Short-term: 28° F to 131° F (-5° C to 55° C) up to 6,000 feet (1,829 meters).

NOTE: Short-term is defined as 96 consecutive hours or less and not more than 15 days in 12 months.

Non-Operating

-40° F to 158° F (-40° C to 70° C)

Elevation

Operating

-197 feet to 6,000 feet (-60 to 1,800 meters) at 104° F (40° C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86° F (30° C)

Vibration profiles

Operating

0.1G, 5-100 Hz, 0.1 octave/minute
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 octave/minute

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3 dB/octave

Site Power Requirements 

The following table lists the 

Unable to show "metadata-from": No such page "_space_variables"
system power requirements:

Prior to connecting to the DC power source, connect the (earth) ground at both the designated grounding terminals on the

Unable to show "metadata-from": No such page "_space_variables"
chassis and at the facility wiring side of the DC supply.

SBC 7000 System Power Requirements

 

SBC 7000

DC Option

Operational DC Voltage (Nominal)

-48

Operational DC voltage (Minimal)

-40

Operational DC voltage (Maximum)

-72

DC Input Treatment

Isolated DC Return

Maximum DC Current

72.5 A

AC Option

Operational AC Voltage (Nominal)

220 VAC @ 50-60 Hz

Maximum AC Current

16 A

Power Cord

An AC power cord is included in SBC shipments for SBCs equipped with AC power supplies.

(North American 20 A 250 VOLT NEMA L6-20P to IEC C19 Connector)

Grounding

BondingBonded to a grounding system utilizing either an Isolated Bonding Network
(Isolated Ground) or a Common Bonding Network (Integrated Ground).

Note

SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process.  The example above is a North American power cord (20 amp 250 volt NEMA L6-20P to IEC C19 connector), which is one of the selections.

Warning

For the DC-powered

Unable to show "metadata-from": No such page "_space_variables"
, the primary over-current protection is provided by the building circuit breaker. This breaker must not exceed 100 A (recommended rating is 80 A) to protect against excess currents, short circuits, and earth faults in accordance to national and/or local codes.

High Amp AC Power Connector

A higher amperage AC connector is used which is different than a normal AC connectors to power the

Unable to show "metadata-from": No such page "_space_variables"
. The connector pin orientation of this higher amperage AC connector is shown below.

High Amperage AC Connector

 
  • No labels