This section contains site planning and requirements information for installing the
Unable to show "metadata-from": No such page "_space_variables"
system.
Site Environmental Requirements
The following table lists the environmental requirements of
Unable to show "metadata-from": No such page "_space_variables"
.
Site Environmental Requirements
Item | Requirement |
---|
SBC 7000 Dimensions | - 19" Rack Width - 17.096" excluding mounting ears
- Maximum depth from Bezel badge label to power supply handle - 23.095"
- 5U High - 8.718 inches
- Weight: 98 lbs
- Mounts in 19 or 23-inch racks
|
Rack Space | - 19" Rack Width - 17.096" excluding mounting ears
- Maximum depth from Bezel badge label to power supply handle - 23.095"
- 5U high - 8.718 inches
- Weight: 98 lbs
- Mounts in 19 or 23-inch racks
|
Server Access Clearance | A minimum 36-inch clearance in front of and behind the chassis. |
Humidity | Short-Term Operating - 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).
NOTE: Short-term is defined as 96 consecutive hours or less, and not more than 15 days in 12 months. |
Full-Term Operating |
Non-operating - Up to 93% non-condensing 100.4° F (37.7° C) maximum wet bulb.
|
Temperature | Operating 41° F to 104° F (5° C to 40° C) up to 6,000 feet (1,829 meters) Short-term: 28° F to 131° F (-5° C to 55° C) up to 6,000 feet (1,829 meters). NOTE: Short-term is defined as 96 consecutive hours or less and not more than 15 days in 12 months. |
Non-Operating -40° F to 158° F (-40° C to 70° C) |
Elevation | Operating -197 feet to 6,000 feet (-60 to 1,800 meters) at 104° F (40° C). 5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86° F (30° C) |
Vibration profiles | Operating 0.1G, 5-100 Hz, 0.1 octave/minute 0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 octave/minute |
Non-operating 5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3 dB/octave |
Site Power Requirements
The following table lists the
Unable to show "metadata-from": No such page "_space_variables"
system power requirements:
Prior to connecting to the DC power source, connect the (earth) ground at both the designated grounding terminals on the
Unable to show "metadata-from": No such page "_space_variables"
chassis and at the facility wiring side of the DC supply.
SBC 7000 System Power Requirements
| SBC 7000 |
---|
DC Option |
---|
Operational DC Voltage (Nominal) | -48 |
---|
Operational DC voltage (Minimal) | -40 |
---|
Operational DC voltage (Maximum) | -72 |
---|
DC Input Treatment | Isolated DC Return |
---|
Maximum DC Current | 72.5 A |
---|
AC Option |
---|
Operational AC Voltage (Nominal) | 220 VAC @ 50-60 Hz |
---|
Maximum AC Current | 16 A |
---|
Power Cord | An AC power cord is included in SBC shipments for SBCs equipped with AC power supplies.
(North American 20 A 250 VOLT NEMA L6-20P to IEC C19 Connector) |
---|
Grounding |
---|
Bonding | Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground). |
---|
Note
SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process. The example above is a North American power cord (20 amp 250 volt NEMA L6-20P to IEC C19 connector), which is one of the selections.
Warning
For the DC-powered
Unable to show "metadata-from": No such page "_space_variables"
, the primary over-current protection is provided by the building circuit breaker. This breaker must not exceed 100 A (recommended rating is 80 A) to protect against excess currents, short circuits, and earth faults in accordance to national and/or local codes.
High Amp AC Power Connector
A higher amperage AC connector is used which is different than a normal AC connectors to power the Unable to show "metadata-from": No such page "_space_variables"
. The connector pin orientation of this higher amperage AC connector is shown below.
High Amperage AC Connector