Site Environmental Requirements

The following table lists the environmental requirements for the

Unable to show "metadata-from": No such page "_space_variables"
platform.

Site Environmental Requirements

Item

Requirement

Server Access Clearance

A minimum clearance of 36 inches in front of and behind the chassis for maintenance access as well as air flow.

Humidity

  

Short-Term Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.

Temperature

Operating
41°F to 104°F (5°C to 40°C) up to 6,000 feet (1,829 meters)
Short-Term: 28°F to 131°F (-5°C to 55°C) up to 6,000 feet (1,829 meters).

Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Non-Operating
-40°F to 158°F (-40°C to 70°C)

Elevation

Operating
-197 feet to 6,000 feet (-60 to 1,800 meters) at 104°F (40°C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86°F (30°C)

Rack Space

Width: 17.16 inch excluding mounting ears
Height: 3.44 inch to fit in 2RU (3.5 inch)
Depth: 21-inch, excluding cable bend radius
Weight: 50 pounds
Mounts in 19-inch or 23-inch racks

Vibration Profiles

Operating
0.1G, 5-100Hz, 0.1 Oct/min
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave

Site Power Requirements

The following table lists the 

Unable to show "metadata-from": No such page "_space_variables"
system power requirements for both AC and DC power options:

SBC 5400 System Power Requirements

 ItemRequirement
DC Power
  • Operational DC Voltage
    (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC
  • DC Input treatment: Isolated
    DC Return
  • Maximum DC current: 36.2A
AC Power
  • Operational AC Voltage (Nominal):
    100-120 V AC or  200-240 V AC
  • Frequency: 50/60 Hz
  • Maximum AC current: 12A/7A
GroundingPower supplies should be bonded to a grounding system
utilizing either an Isolated Bonding Network (Isolated Ground)
or a Common Bonding Network (Integrated Ground).