You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »

In this section:

This section contains information on site planning and requirements for installing the SBC 5400 system.

Site Environmental Requirements

The following table lists the environmental requirements for the SBC 5400.

Site Environmental Requirements

Item

Requirement

Rack Dimensions

  • Maximum width - 17.16 inches, excluding mounting ears
  • Maximum depth - 21 inches, excluding cable bend radius
  • Maximum height - 3.44 inches
  • Weight: 50 pounds
  • Mounts in 19-inch or 23-inch racks

Server Access Clearance

A minimum clearance of 36 inches in front of and behind the chassis for maintenance access as well as air flow.

Humidity

  

Short-Term Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.

Temperature

Operating
41°F to 104°F (5°C to 40°C) up to 6,000 feet (1,829 meters)
Short-Term: 28°F to 131°F (-5°C to 55°C) up to 6,000 feet (1,829 meters).

Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Non-Operating
-40°F to 158°F (-40°C to 70°C)

Elevation

Operating
-197 feet to 6,000 feet (-60 to 1,800 meters) at 104°F (40°C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86°F (30°C)

Rack Space

Width: 17.16 inch excluding mounting ears
Height: 3.44 inch to fit in 2RU (3.5 inch)
Depth: 21-inch, excluding cable bend radius
Weight: 50 pounds
Mounts in 19-inch or 23-inch racks

Vibration Profiles

Operating
0.1G, 5-100Hz, 0.1 Oct/min
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave

Site Power Requirements

The following table lists the SBC 5400 system power requirements for both AC and DC power options:

SBC 5400 System Power Requirements

 ItemRequirement
DC Power
  • Operational DC Voltage
    (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for
    chassis: -40 V DC
  • Maximum operation DC voltage for
    chassis: -72 V DC
  • DC Input treatment: Isolated
    DC Return
  • Maximum DC current: 36.2A
AC Power
  • Operational AC Voltage (Nominal):
    100-120 V AC or  200-240 V AC
  • Frequency: 50/60 hz
  • Maximum AC current: 12A/7A
GroundingPower supplies should be bonded to a grounding system
utilizing either an Isolated Bonding Network (Isolated Ground)
or a Common Bonding Network (Integrated Ground).

  • No labels