chassis slot 0 contains the Core Server Card (CSC) module which is used for control and data plan processing. The CSC contains two (2) High Availability ports (10G), two (2) Management Ports (10MB/100MB/1G), and Redundant 10G Packet Ports (2 primary + 2 secondary). The CSC product code is SBC-7000-CSC.
SBC 7000 Core Server Card
The following items are needed to replace a CSC:
- Electrostatic discharge (ESD) strap
- Replacement CSC
- A #2 Phillips-head screwdriver
Replacing Core Server Card
Safety shield cover must be intact when system is powered on.
To replace a CSC, do the following:
- Perform a graceful shutdown of the
Unable to show "metadata-from": No such page "_space_variables"
system through BMC GUI. - Attach an Electrostatic Discharge wrist strap by using the ESD grounding point on the back panel of the chassis (see Connecting Electrostatic Discharge Wrist Strap on SBC 7000 for details).
- Remove all the existing connections from all the ports.
Unscrew the thumb screws using #2 Phillips-head screwdriver, open release levers on each side, and pull the CSC module out.
SBC 7000 Core Server Card pulled out
- To replace, insert the new module to the correct slot, push the CSC module completely.
- Close the release levers.
- Tighten the thumb screws using #2 Phillips-head screwdriver.
- Re-connect all the ports.
- Start the
Unable to show "metadata-from": No such page "_space_variables"
system through BMC GUI.
CRU Storage
All
Unable to show "metadata-from": No such page "_space_variables"
CRUs are shipped in electrostatic discharge (ESD) bags and must be handled by using appropriate ESD precautions. The storage environment for these CRUs are:
- Humidity must be less than 95% (non-condensing).
- Temperature must be between -40C and +70C.
The ESD Susceptibility symbol warns of the presence of Sonus devices susceptible to electrostatic discharge. Do not handle equipment without wearing a properly grounded ESD wrist strap.