Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Panel
borderColorgreen
bgColortransparent
borderWidth2

Back to Table of Contents

Back to Installing SBC 5400 Hardware

Back to SBC 5400 Hardware Installation Overview

Panel

In this section:

Table of Contents
maxLevel4
minLevel2

 

This section contains information on site planning and requirements for installing the

Spacevars
0model5
system.

Site Environmental Requirements

The following table lists the environmental requirements for the

Spacevars
0model5
platform.

Caption
0Table
1Site Environmental Requirements

Item

Requirement

Server Access Clearance

A minimum clearance of 36 inches in front of and behind the chassis for maintenance access as well as air flow.

Humidity

  

Short-Term* Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.

Temperature

Operating

41°F to 104°F (5°C to 40°C) up to 6,000 feet (1,829 meters)
Short-Term*: 28°F to 131°F (-5°C to 55°C) up to 6,000 feet (1,829 meters).

Non-Operating

-40°F to 158°F (-40°C to 70°C)

Elevation

Operating

-197 feet to 6,000 feet (-60 to 1,800 meters) at 104°F (40°C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86°F (30°C)

Rack Space

Width: 17.16 inch excluding mounting ears
Height: 3.44 inch to fit in 2RU (3.5 inch)
Depth: 21-inch, excluding cable bend radius
Weight: 50 pounds
Mounts in 19-inch or 23-inch racks

Vibration Profiles

Operating

0.1G, 5-100Hz, 0.1 Oct/min
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave

Note
iconfalse

*  Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Site Power Requirements

The following table lists the 

Spacevars
0model5
system power requirements for both AC and DC power options:
Caption
0Table
1SBC 5400 System Power Requirements
3SBC 5400 System Power Requirements

...

 

...

SBC 5400

DC

...

Option

Operational DC Voltage

...

(Nominal)

...

-48

...

...

Operational DC voltage

...

(Minimal)

...

-40

...

...

Operational DC voltage

...

(Maximum)

...

-72

...

DC Input

...

Treatment

Isolated

...

DC Return

Maximum DC

...

Current

36.

...

2 A

AC

...

Option

Operational AC Voltage (Nominal)

...

100-120

...

VAC @ 50-60 Hz
or 
200-240

...

VAC @ 50-60 Hz

Maximum AC

...

Current

12 A / 7 A

Power Cord

An AC power cord is included in SBC shipments for SBCs equipped with AC power supplies.

Image Added

(North American 15 A 125 VOLT NEMA 5-15P to IEC C19 Connector)

Grounding

BondingBonded to a grounding system

...

utilizing either

...

an Isolated Bonding Network
(Isolated Ground)

...

or a Common Bonding Network (Integrated Ground).

Info
titleNote

SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process.  The example above is a North American power cord (15 amp 125 volt NEMA 5-15P to IEC C19 connector), which is one of the selections.

 

Pagebreak