After installing the 

Spacevars
0series2
chassis to a rack and attaching necessary cables, you are now ready to install power and ground cables and apply power to the SBC. The 
Spacevars
0series2
is capable of dual redundant AC or DC power.

The standard

Spacevars
0series2
is shipped with two power supplies. Please contact your sales representative for more information.

Warning
Before connecting to power, you must connect the chassis ground lug to the SBC chassis.


Caption
0Table
1SBC 7000 Power Requirements


DSP ConfigurationACDC

Minimum: 180 Vrms
Nominal: 200-240 Vrms
Maximum: 264 Vrms

Minimum: 40 Vdc
Nominal: 48 Vdc
Maximum: 60 Vdc




AmpsWattsAmpsWatts
SBC 7000 without DSP Card7.0121723938
SBC 7000+1*DSP Card9.01571331326
SBC 7000+2*DSP Cards111940421679
SBC 7000+3*DSP Cards132326512059
SBC 7000+4*DSP Cards152724622473



Note

All power ratings in the table reflect fans running at high speed.

Anchor
grounding_chassis
grounding_chassis

Grounding the SBC 7000 Chassis

The following procedure explains how to ground the

Spacevars
0series2
to local earth using a 7/16 inch wrench:

  1. Locate the chassis grounding studs on the back of the chassis.
  2. Attach the two hole chassis ground lug PN 501-00526 to 

    Spacevars
    0series2
    using two flat washers PN 511-00376, two split lock washers PN 510-00056, and two hex nuts PN 511-00046.

    Caption
    0Figure
    1Chassis Grounding Lug Location


  3. Secure the other end of the grounding cable to the earth ground in the building. You can secure the grounding cable to a proper grounding point on the rack, as long as the rack is properly grounded to the earth ground in the building.
Note

Use the recommended 4AWG stranded copper cable for DC SBC 7000.


Note

Connect the chassis to local earth ground such that any possible charge is carried off to the earth thus eliminating the risk of shock.

Routing the Power Cables

Route the power cables so that the left power supply cables connect from left side and the right power supply cables connect from right. This prevents one power supply cable from getting in the way of the other one in case it needs to be removed individually.

Connecting to AC Power Source and Powering On

The following procedure explains how to connect to the Tectrol-specific AC power and powering on the switch:

  1. For each AC power supply, insert the supplied AC power cord's female connector to the power supply AC receptacle at the rear of the chassis (shown in the following figure).

    Caption
    0Figure
    1SBC 7000 Chassis Tectrol AC Power Location


  2. Connect the supplied power cords to the local AC power source.

    Caption
    0Figure
    1Connecting Tectrol AC Power Supply


  3. Turn on your local AC power source.

Disconnecting from AC Power Source


The following procedure explains how to disconnect from your local AC power source:

  1. Perform a graceful shutdown of the 
    Spacevars
    0series2
    system through BMC.
  2. Turn off your local AC power source.
  3. Remove the power cord.

Connecting to DC Power Source and Powering On

The following procedure explains how to connect an 

Spacevars
0series2
power supply to the DC Power and power on the switch. If two power supplies are installed, both need to be connected to a power source before powering on the system.

Note

Identify the correct size fuse(s) for your configuration and wire gauge before applying DC power to a switch; not to exceed 100A (recommended rating is 80A) fuse. Also, ensure to switch off the power supply before installing the cables.

  • Remove the clear plastic terminal cover and set it aside. Check the chassis ground is connected to the 2-post terminal lug next to the power supply bay. 
  • Connect ground cable (green) to the lug to the right of the DC power terminal posts as shown in the below figure:

    Caption
    0Figure
    1SBC DC Terminal Connections

    Image Removed

  • Use a voltmeter to verify that no voltage is present on DC input power cables.
  • Attach the DC return cable (black) to the "+" terminal.
  • Attach the -48V cable (red) to the "-" terminal.
  • Reattach the clear plastic terminal cover.
  • If applicable, attach the other end of the supplied DC power cables to DC power source.

    Warning

    Do not apply DC power to the DC Power supply prior to hot-inserting the supply into the chassis.

  • Turn on DC power source.
  • Disconnecting from DC Power Source

    The following procedure explains how to disconnect DC power from 

    Spacevars
    0series2
    series chassis:

    1. Perform a graceful shutdown of the 
      Spacevars
      0series2
      system through BMC.
    2. Turn off the local DC power source.
    3. Remove the clear plastic terminal cover and set it aside.
    4. Remove the DC power cables from the terminals, and re-attach the nuts.
    5. Remove the ground cable from the power supply, and re-attach the nut.
    Warning

    Do not remove the DC Power supply without first turning off the power to the power supply being removed from the chassis.

    Removing the Power Supply

    Warning

    Remove DC (or AC) power from the power supply and remove the power cables from power supply before attempting this procedure.

    To remove the AC or DC power supply from the chassis, perform the following steps:

    1. Follow the procedure above for disconnecting from AC or DC power source.
    2. Wait until the fans in the power supply completely stop spinning.
    3. Push the green or black integrated lever towards your left to disengage the power supply module.
    4. Pull the power supply out of the power supply slot.

    Table of Contents

    Panel

    In this section:

    Table of Contents
    maxLevel2
    minLevel2

    After installing the 

    Spacevars
    0series2
    chassis to a rack and attaching necessary cables, you are now ready to install power and ground cables and apply power to the SBC. The 
    Spacevars
    0series2
    is capable of dual redundant AC or DC power.

    The standard

    Spacevars
    0series2
    is shipped with two power supplies. Please contact your sales representative for more information.

    Warning
    Before connecting to power, you must connect the chassis ground lug to the SBC chassis.
    Caption
    0Table
    1SBC 7000 Power Requirements
    DSP ConfigurationACDC

    Minimum: 180 Vrms
    Nominal: 200-240 Vrms
    Maximum: 264 Vrms

    Minimum: 40 Vdc
    Nominal: 48 Vdc
    Maximum: 60 Vdc

    AmpsWattsAmpsWattsSBC 7000 without DSP Card7.0121723938SBC 7000+1*DSP Card9.01571331326SBC 7000+2*DSP Cards111940421679SBC 7000+3*DSP Cards132326512059SBC 7000+4*DSP Cards152724622473
    Note

    All power ratings in the table reflect fans running at high speed.

    Anchorgrounding_chassisgrounding_chassis

    Grounding SBC 7000 Chassis

    The following procedure explains how to ground the

    Spacevars
    0series2
    to local earth using a 7/16 inch wrench:

  • Locate the chassis grounding studs on the back of the chassis.
  • Attach the two hole chassis ground lug PN 501-00526 to 

    Spacevars
    0series2
    using two flat washers PN 511-00376, two split lock washers PN 510-00056, and two hex nuts PN 511-00046.

    Caption
    0Figure
    1Chassis Grounding Lug Location

    Image Removed

  • Secure the other end of the grounding cable to the earth ground in the building. You can secure the grounding cable to a proper grounding point on the rack, as long as the rack is properly grounded to the earth ground in the building.
  • Note

    Use the recommended 4AWG stranded copper cable for DC SBC 7000.

    Note

    Connect the chassis to local earth ground such that any possible charge is carried off to the earth thus eliminating the risk of shock.

    Routing the Power Cables

    Route the power cables so that the left power supply cables connect from left side and the right power supply cables connect from right. This prevents one power supply cable from getting in the way of the other one in case it needs to be removed individually.

    Connecting to AC Power Source and Powering On

    The following procedure explains how to connect to the AC power and to the ABB-specific AC power and powering on the switch:

    1. For each AC power supply, insert the supplied AC power cord's female connector to the power supply AC receptacle at the rear of the chassis (shown in the following figure).

      Caption
      0Figure
      1SBC 7000 Chassis ABB AC Power Location

      Image Modified


    2. Connect the supplied power cords to the local AC power source.

      Caption
      0Figure
      1Connecting ABB AC Power Supply

      Image Modified


    3. Turn on your local AC power source.

    Disconnecting from the AC Power Source

    The following procedure explains how to disconnect from your local AC power source:

    1. Perform a graceful shutdown of the 
      Spacevars
      0series2
      system through BMC.
    2. Turn off your local AC power source.
    3. Remove the power cord.

    Connecting to the DC Power Source and Powering On

    The following procedure explains how to connect an 

    Spacevars
    0series2
    power supply to the DC Power and power on the switch. If two power supplies are installed, both need to be connected to a power source before powering on the system.

    Note

    Identify the correct size fuse(s) for your configuration and wire gauge before applying DC power to a switch; not to exceed 100A (recommended rating is 80A) fuse. Also, ensure to switch off the power supply before installing the cables.

    1. Remove the clear plastic terminal cover and set it aside. Check the chassis ground is connected to the 2-post terminal lug next to the power supply bay. 
    2. Connect ground cable (green) to the lug to the right of the DC power terminal posts as shown in the below figure:

      Caption
      0Figure
      1SBC DC Terminal Connections


    3. Use a voltmeter to verify that no voltage is present on DC input power cables.
    4. Attach the DC return cable (black) to the "+" terminal.
    5. Attach the -48V cable (red) to the "-" terminal.
    6. Reattach the clear plastic terminal cover.
    7. If applicable, attach the other end of the supplied DC power cables to DC power source.

      Warning

      Do not apply DC power to the DC Power supply prior to hot-inserting the supply into the chassis.


    8. Turn on DC power source.

    Disconnecting

    from

    From the DC Power Source

    The following procedure explains how to disconnect DC power from 

    Spacevars
    0series2
    series chassis:

    1. Perform a graceful shutdown of the 
      Spacevars
      0series2
      system through BMC.
    2. Turn off the local DC power source.
    3. Remove the clear plastic terminal cover and set it aside.
    4. Remove the DC power cables from the terminals, and re-attach the nuts.
    5. Remove the ground cable from the power supply, and re-attach the nut.
    Warning

    Do not remove the DC Power supply without first turning off the power to the power supply being removed from the chassis.

    Removing the Power Supply

    Warning

    Remove DC (or AC) power from the power supply and remove the power cables from power supply before attempting this procedure.

    To remove the AC or DC power supply from the chassis, perform the following steps:

    1. Follow the procedure above for disconnecting from AC or DC power source.
    2. Wait until the fans in the power supply completely stop spinning.
    3. Push the green or black integrated lever towards your left to disengage the power supply module.
    4. Pull the power supply out of the power supply slot.