This section contains information on site planning and requirements for installing the
system.Site Environmental Requirements
The following table lists the environmental requirements for the
platform. Caption |
---|
0 | Table |
---|
1 | Site Environmental Requirements |
---|
|
Item | Requirement |
---|
Server Access Clearance | A minimum clearance of 36 inches in front of and behind the chassis for maintenance access as well as air flow. |
---|
Humidity | Short-Term* Operating - 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).
|
---|
|
Note |
---|
Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year. |
Full-Term Operating | Non-operating - Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.
| Temperature | Operating 41°F to 104°F (5°C to 40°C) up to 6,000 feet (1,829 meters) Short-Term*: 28°F to 131°F (-5°C to 55°C) up to 6,000 feet (1,829 meters). |
---|
|
...
...
Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.
Non-Operating -40°F to 158°F (-40°C to 70°C) | Elevation | Operating -197 feet to 6,000 feet (-60 to 1,800 meters) at 104°F (40°C). 5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86°F (30°C) |
---|
Rack Space | Width: 17.16 inch excluding mounting ears Height: 3.44 inch to fit in 2RU (3.5 inch) Depth: 21-inch, excluding cable bend radius Weight: 50 pounds Mounts in 19-inch or 23-inch racks |
---|
Vibration Profiles | Operating 0.1G, 5-100Hz, 0.1 Oct/min 0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min |
---|
Non-operating 5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave |
|
Note |
---|
|
* Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year. |
Site Power Requirements
The following table lists the
system power requirements for both AC and DC power options: Caption |
---|
0 | Table |
---|
1 | SBC 5400 System Power Requirements |
---|
3 | SBC 5400 System Power Requirements |
---|
|
...
...
...
Option |
---|
Operational DC Voltage |
---|
|
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
Option |
---|
Operational AC Voltage (Nominal) |
---|
|
...
...
VAC @ 50-60 Hz or 200-240 |
|
...
...
Current | 12 A / 7 A |
---|
Power Cord | An AC power cord is included in SBC shipments for SBCs equipped with AC power supplies. Image Added (North American 15 A 125 VOLT NEMA 5-15P to IEC C19 Connector) |
---|
Grounding |
---|
Bonding | Bonded to a grounding system |
---|
|
...
...
an Isolated Bonding Network (Isolated Ground) |
|
...
or a Common Bonding Network (Integrated Ground). |
|
Info |
---|
|
SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process. The example above is a North American power cord (15 amp 125 volt NEMA 5-15P to IEC C19 connector), which is one of the selections. |