This section describes the grounding requirements for Sonus
SBC 1000/2000 systems.
Grounding Requirements
Multiexcerpt |
---|
MultiExcerptName | ground-wiring |
---|
|
Sonus SBC 1000/2000 Series equipment must be grounded to the building ground network. For ground wire specifics, see the tables below for the United States, Canada and Europe. Note |
---|
Only qualified service personnel should perform the electrical procedures for grounding wire installation. |
United States and Canada Grounding ConnectionsRequirements | |
---|
Minimum Wire Size | 14 AWG | Minimum Voltage Rating | 300 V | Conductor | Stranded |
Europe Grounding ConnectionsRequirements | |
---|
Minimum Wire Size | 1.63 mm | Minimum Voltage Rating | 300 V | Conductor | Stranded |
|
Connecting the
...
Ribbon SBC 1000/2000 Chassis to Earth Ground
When installing the chassis, connect the earth ground wires from the Sonus
SBC 1000/2000 chassis to the facility ground bus.
...
Panel |
---|
title | Ground Connections on Left Rear Panel of the Sonus Ribbon SBC 2000 |
---|
|
|
Panel |
---|
title | Ground Connections on Left Rear Panel of the Sonus Ribbon SBC 1000 |
---|
|
|
To Ground the
...
SBC 2000 System- Locate the ground connection bolt at the back left corner of the chassis.
- For Sonus SBC 2000, attach 14 AWG copper wire and a 1-hole UL approved lug to the grounding bolt. Use Panduit PN14-6R or equivalent.
To Ground the
...
SBC 1000 System- Locate the ground connection bolt at the back left corner of the chassis.
- For Sonus SBC 1000, attach 14 AWG copper wire and a 1-hole UL approved lug to the grounding bolt. Use Panduit PN14-6R or equivalent.