Warning |
---|
...
Connect the chassis ground lug to the SBC chassis before connecting power. |
Caption | ||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||||||||||||||
|
...
|
...
|
...
|
...
|
...
|
...
|
...
|
...
|
Note |
---|
This is estimated power consumption. All power measurements were taken with fans running at high speed. |
Anchor | ||||
---|---|---|---|---|
|
...
Spacevars | ||
---|---|---|
|
The following procedure explains how to ground
...
the
Spacevars | ||
---|---|---|
|
Attach the two hole chassis ground lug PN 300-30016 to the
...
Spacevars | ||
---|---|---|
|
Caption | ||||
---|---|---|---|---|
| ||||
Note |
---|
Connect the chassis to local earth ground |
...
so that any possible charge is carried off to the earth thus eliminating the risk of shock. |
Sonus recommends to route the power cables so that the top power supply cables connect from above and the bottom power supply cables connect from below. This prevents one power supply cable from getting in the way of the other one in case it needs to be removed individually.
The following procedure explains how to connect to the AC power and powering on the switch:
For each AC power supply, insert the supplied AC power cord
...
female connector to the power supply AC receptacle at the rear of the chassis (shown in the following figure).
Caption | ||||
---|---|---|---|---|
| ||||
In a dual-redundant power supply configuration, the power supplies are hot-swappable meaning that it may be replaced without removing the power supply of SBC platform (provided that the redundant power supply is operational).
Note | ||
---|---|---|
| ||
Before replacing a power supply in a redundant power supply configuration, verify the status of the redundant power supply. The “POK” LED status must be “solid green”. Removing the power supply when the redundant supply does not show a solid green status, may cause the system to power down. Contact Sonus customer support if required. |
The following table describes the status of AC power supply.
Caption | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||
|
The following procedure explains how to disconnect from your local AC power source:
...
Spacevars | ||
---|---|---|
|
The following procedure explains connecting
...
an
Spacevars | ||
---|---|---|
|
Note |
---|
Identify the correct size fuse(s) for your configuration and wire gauge before applying DC power to a switch. Also, ensure to switch off the power supply before installing the cables. |
Connect ground cable (green) to the screw located above the DC power terminal posts as shown in the below figure:
Caption | ||||
---|---|---|---|---|
| ||||
...
If applicable, attach the other end of the supplied DC power cables to DC power source.
Warning |
---|
Do not apply DC power to the DC Power supply prior to hot-inserting the supply into the chassis. |
In a dual-redundant power supply configuration, the power supplies are hot-swappable meaning that it may be replaced without powering down
...
the
Spacevars | ||
---|---|---|
|
Note | ||
---|---|---|
| ||
Before replacing a power Supply in a redundant power supply configuration, verify the status of the redundant power supply. The “POK” LED status must be “solid green”. Removing the power supply when the redundant supply does not show a solid green status, may cause the system to power down. Contact Sonus Customer Support if required. |
The following table describes the status of DC power supply.
Caption | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||
|
The following procedure explains how to disconnect DC power
...
from
Spacevars | ||
---|---|---|
|
...
Spacevars | ||
---|---|---|
|
Warning |
---|
Do not remove the DC Power supply without first turning off the power to the power supply being removed from the chassis. |
Warning |
---|
Remove DC power from the power supply and remove the power cables from power supply before attempting this procedure. |
To remove the AC or DC power supply from the chassis, perform the following steps:
Refer to the following figures for integrated lever locations:
Caption | ||||
---|---|---|---|---|
| ||||
Caption | ||||
---|---|---|---|---|
| ||||