In a dual redundant power supply configuration, the power supplies are hot-swappable meaning that a power supply may be replaced without powering down the
Spacevars | ||
---|---|---|
|
Note | ||
---|---|---|
| ||
Before replacing a power supply in a redundant power supply configuration, verify the status of the redundant power supply. The “POK” LED status must be “solid green”. Removing the power supply when the redundant supply does not show a solid green status, may cause the system to power down. Contact Sonus Customer Support if required. |
Caption | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||
|
Note |
---|
The chassis is shipped with one power supply, unless a second power supply is added to the order. |
Note |
---|
To prevent damage from electrostatic discharge, an ESD strap is provided in the accessory kit. See Connecting ESD Wrist Strap to install it. |
Perform the following procedure to replace a power supply:
Disconnect the AC power cable from the AC power supply as shown below.
Caption | ||||
---|---|---|---|---|
| ||||
Disengage the AC power supply by moving the latch to the left as shown below.
Caption | ||||
---|---|---|---|---|
| ||||
Pull on the loop handle to slide the AC power supply out of the
Spacevars | ||
---|---|---|
|
Caption | ||||
---|---|---|---|---|
| ||||
Spacevars | ||
---|---|---|
|
Reconnect the AC power cable, as shown below.
Caption | ||||
---|---|---|---|---|
| ||||
Tooltip | ||
---|---|---|
| ||
All
Spacevars | ||
---|---|---|
|
The storage environment for these CRUs are: