Panel | ||||
---|---|---|---|---|
In this section:
|
Tooltip | ||
---|---|---|
| ||
The
Spacevars | ||
---|---|---|
|
Spacevars | ||
---|---|---|
|
The figure DC Power Supply below depicts a dual redundant configuration. The DC power supply Customer Replaceable Unit (CRU) product codes are:
Caption | ||||||
---|---|---|---|---|---|---|
| ||||||
Note | ||
---|---|---|
| ||
Before replacing a power supply in a redundant Power Supply configuration, verify the status of the redundant Power Supply. The Power OK (POK) LED status must be solid green. Removing the power supply when the redundant Power Supply does not show a solid green status, may cause the system to power down. Contact Sonus Customer Support if required. |
Tooltip | ||
---|---|---|
| ||
To replace a faulty power supply, the following items are needed:
Include Page | ||||
---|---|---|---|---|
|
Perform the following procedure to replace a Power Supply:
Disconnect RTN and -48V connections by loosening two terminal nuts with the 3/8" socket.
Caption | ||||
---|---|---|---|---|
| ||||
Pull out the DC Power Supply from the SBC chassis.
Caption | ||||
---|---|---|---|---|
| ||||
Install the replacement DC Power Supply into the
Spacevars | ||
---|---|---|
|
Warning |
---|
Power supply must be inserted and fully placed before connecting power cables back. |
Tooltip | ||
---|---|---|
| ||
All
Spacevars | ||
---|---|---|
|
The storage environment for these CRUs is:
Include Page | ||||
---|---|---|---|---|
|
Pagebreak |
---|