This section contains site planning and requirements information for installing the

Spacevars
0series2
system.

Site Environmental Requirements

The following table lists the environmental requirements of

Spacevars
0series2
.

Caption
0Table
1Site Environmental Requirements
 

Item

Requirement

SBC 7000 Dimensions

  • 19" Rack Width - 17.096" excluding mounting ears
  • Maximum depth from Bezel badge label to power supply handle - 23.095"
  • 5U High - 8.718 inches
  • Weight: 98 lbs
  • Mounts in 19 or 23-inch racks
Rack Space
  • 19" Rack Width - 17.096" excluding mounting ears
  • Maximum depth from Bezel badge label to power supply handle - 23.095"
  • 5U high - 8.718 inches
  • Weight: 98 lbs
  • Mounts in 19 or 23-inch racks

Server Access Clearance

A minimum 36-inch clearance in front of and behind the chassis.

Humidity

  

Short-Term Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).

NOTE: Short-term is defined as 96 consecutive hours or less, and not more than 15 days in 12 months.

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4° F (37.7° C) maximum wet bulb.

Temperature

Operating

41° F to 104° F (5° C to 40° C) up to 6,000 feet (1,829 meters)
Short-term: 28° F to 131° F (-5° C to 55° C) up to 6,000 feet (1,829 meters).

NOTE: Short-term is defined as 96 consecutive hours or less and not more than 15 days in 12 months.

Non-Operating

-40° F to 158° F (-40° C to 70° C)

Elevation

Operating

-197 feet to 6,000 feet (-60 to 1,800 meters) at 104° F (40° C).
5,900 feet to 13,100 feet (1,800 to 4,000 meters) at 86° F (30° C)

Vibration profiles

Operating

0.1G, 5-100 Hz, 0.1 octave/minute
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 octave/minute

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3 dB/octave

Site Power Requirements 

The following table lists the 

Spacevars
0series2
system power requirements:

Note

Prior to connecting to the DC power source, connect the (earth) ground at both the designated grounding terminals on the

Spacevars
0series2
chassis and at the facility wiring side of the DC supply.

Caption
0Table
1SBC 7000 System Power Requirements
3SBC 7000 System Power Requirements

 

SBC 7000

DC Option

Operational DC Voltage (Nominal)

-48

Operational DC voltage (Minimal)

-40

Operational DC voltage (Maximum)

-72

DC Input Treatment

Isolated DC Return

Maximum DC Current

72.5 A

AC Option

Operational AC Voltage (Nominal)

220 VAC @ 50-60 Hz

Maximum AC Current

16 A

Power Cord

An AC power cord is included in SBC shipments for SBCs equipped with AC power supplies.

(North American 20 A 250 VOLT NEMA L6-20P to IEC C19 Connector)

Grounding

BondingBonded to a grounding system utilizing either an Isolated Bonding Network
(Isolated Ground) or a Common Bonding Network (Integrated Ground).

Note
iconfalse

Note

SBCs shipped with AC power supplies include a customer-selectable, country-specific power cord that is chosen during the system quoting process.  The example above is a North American power cord (20 amp 250 volt NEMA L6-20P to IEC C19 connector), which is one of the selections.

Warning
titleWarning

For the DC-powered

Spacevars
0series2
, the primary over-current protection is provided by the building circuit breaker. This breaker must not exceed 100 A (recommended rating is 80 A) to protect against excess currents, short circuits, and earth faults in accordance to national and/or local codes.

High Amp AC Power Connector

A higher amperage AC connector is used which is different than a normal AC connectors to power the

Spacevars
0series2
. The connector pin orientation of this higher amperage AC connector is shown below.

Caption
0Figure
1High Amperage AC Connector