tipUse ESD protective device

Image Modified

The Fan Assembly, a Customer Replaceable Unit (CRU), available behind the front bezel. There are four assemblies and each assembly contains a pair of fans, as shown in

...

figure Fan Assembly below. The Fan Assembly product code is SBC-7000-FANTRAY.

Caption
0Figure
1Fan Assembly
3Fan Assembly

Image Modified

The Fan Assemblies are hot-swappable that is, a Fan Assembly may be replaced without powering down the 

Spacevars
0series2
platform.

Parts and Tools Required

Tooltip
tipESD protective device

Image Modified

The following items are needed to replace a fan assembly:

  • Electrostatic discharge (ESD) strap
  • The Replacement Fan Assembly
  • Torque driver with a #2 Phillips bit.

Include Page
ESD_wriststrap_7K
ESD_wriststrap_7K

Replacing the Fan Assembly

Perform the following steps to replace the Fan Assembly:

  1. Remove the front bezel from the chassis (see SBC 7000 Series Bezel  for procedure).
  2. Identify the faulty Fan Assembly by checking the Fan Assembly LED. Fan faults are indicated by turned off LED, or amber LED. The LED is at the right hand bottom of that respective Fan Assembly.
  3. Unscrew the captive fastener on the Fan Assembly using torque driver with a #2 Phillips bit (as shown in the figure).

  4. Using two handles at the top and the bottom, pull the Fan Assembly from the system.

    Caption
    0Figure
    1Removing the Fan Assembly

    Image Modified

    Note

    Whenever a Fan Assembly is nonfunctional or removed, the speed of the three remaining Fan Assemblies increases to compensate for the missing fan.


  5. Insert the new Fan Assembly to the same position.
  6. Tighten the captive fastener to 6 in-lb using the torque driver.

  7. Verify that the Fan Status LED is green. The LED is at the right hand bottom of the Fan Assembly.

    Caption
    0Figure
    1Fan Assembly status indicator

    Image Modified

  8. Remove the ESD wrist strap from the chassis.

  9. Reinstall the front panel bezel.

  10. From the application, verify that the Fan Failure alarms are not generated.

  11. Verify that the fan failure LED on the front panel is OFF.

CRU Storage

Tooltip
tipESD protective device

Image Modified

All 

Spacevars
0series2
CRUs are shipped in electrostatic discharge bags and must be handled by using appropriate ESD precautions.

 The storage environment for these CRUs are:

  • Humidity must be less than 95% (non-condensing).
  • Temperature must be between -40C and +70C.