1Site Environmental Requirements
 

Item

Requirement

SBC 7000 Dimension

  • 19" Rack Width - 17.096" excluding mounting ears
  • Maximum depth from Bezel badge label to power supply handle - 23.095"
  • 5U High - 8.718 inches
  • Weight: 98lbs
  • Mounts in 19 or 23 inch racks
Rack Space
  • 19" Rack Width - 17.096" excluding mounting ears
  • Maximum depth from Bezel badge label to power supply handle - 23.095"
  • 5U High - 8.718 inches
  • Weight: 98lbs
  • Mounts in 19 or 23 inch racks

Server Access Clearance

A minimum of 36 inch clearance in both front and rear of the chassis.

Humidity

  

Short-Term Operating

  • 5% to 90% non-condensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs. water/2.205 lbs. dry air).
Note

Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

Full-Term Operating

  • 5% to 85%

Non-operating

  • Up to 93% non-condensing 100.4°F (37.7°C) maximum wet bulb.

Temperature

Operating
41°F to 104°F (5°C to 40°C) up to 6000 feet (1829 meters)
Short-Term: 28°F to 131°F (-5°C to 55°C) up to 6000 feet (1829 meters).

Note

Short-Term is defined as 96 consecutive hours or less and not more than 15 days in a year.

 

Non-Operating
-40°F to 158°F (-40°C to 70°C)

Elevation

Operating
-197 feet to 6000 feet (-60 to 1800 meters) at 104°F (40°C).
5900 feet to 13100 feet (1800 to 4000 meters) at 86°F (30°C)

Vibration profiles

Operating
0.1G, 5-100Hz, 0.1 Oct/min
0.1G (x,y axis); 0.15G (z axis), 5-500Hz, 1 Oct/min

 

Non-operating
5-20 Hz 0.01 g2/Hz and 20-200 Hz - 3dB/octave

Site Power Requirements

The following table lists the 

Spacevars
0series2
system power requirements:

Caption
0Table
1SBC 7000 System Power Requirements
 
 SBC 7000
DC Option
  • Operational DC Voltage (Nominal) for chassis: -48 V DC
  • Minimum operation DC voltage for chassis: -40 V DC
  • Maximum operation DC voltage for chassis: -72 V DC
  • DC Input treatment: Isolated DC Return
  • Maximum DC current: 72.5A

    Warning
    titleWarning

    For DC powered

    Spacevars
    0series2
    , the primary over-current protection is provided by the building circuit breaker. This breaker must not exceed 100A (recommended rating is 80A) and protects against excess currents, short circuits, and earth faults in accordance to national and/or local codes.

    Note
    titleNote

    Prior to connecting to the DC power source, connect the (earth) ground at both the designated grounding terminals on the SBC 7000 chassis and at the facility wiring side of the DC supply.

AC Option
  • Operational AC Voltage (Nominal): 220 V AC
  • Frequency: 50/60 Hz
  • Maximum AC current for 220 V AC: 16A
Grounding

Bonded to a grounding system utilizing either an Isolated Bonding Network (Isolated Ground) or a Common Bonding Network (Integrated Ground).

Connection to AC Power Source and Powering On

...