This section describes the method to upgrade the
Spacevars | ||
---|---|---|
|
Warning |
---|
For an SBC HA pair with ePSX installed, perform a manual switchover on the current Active SBC and allow the system to successfully complete the process prior to performing the BMC upgrade to avoid impairments to ePSX database. |
The following procedure describes how to upgrade the firmware from the BMC web GUI.
Login to the BMC using the following credentials:
Username: root
Password: superuser
Caption | ||||
---|---|---|---|---|
| ||||
The BMC main screen displays.
Caption | ||||
---|---|---|---|---|
| ||||
Click Firmware Update. The Firmware Update screen displays.
Caption | ||||
---|---|---|---|---|
| ||||
Click Browse, and from the Open dialog browse to and select select firmware-7X00-V01.34.00-R000.V<release>.img firmware image. To determine the exact firmware version, see SBC Release Information for guidance.
The chosen file displays next to the Browse button.
Caption | ||||
---|---|---|---|---|
| ||||
Click Upload.
Note |
---|
The firmware image is a 26MB file and takes few minutes to upload based on the network. |
Once upload is completed, the Firmware Update screen displays the firmware images and its details.
Caption | ||||
---|---|---|---|---|
| ||||
Note |
---|
The above screen displays the list of entities, which are updated. If both the Old Version and New Version are same, then the update status displays as "No". |
Click Confirm to continue. The upgrade progress bar displays on the screen.
Note |
---|
This is a service affecting procedure and will power off the host side of SBC. |
After the firmware upgrade is completed, the following screen displays. The BMC automatically restarts.
Caption | ||||
---|---|---|---|---|
| ||||
Note |
---|
Once the upgrade completes, BMC and host reboots automatically. Verify that the SBC starts and sync with its peer server before proceeding further. |
Close the BMC GUI.
Clear the browser cache and login into the BMC GUI again.
...